About this calculator
A solar panel’s rating (W at STC) is measured at 1000 W/m² of sun and a cell temperature of 25 °C. In real use the sun is weaker, the cells are hotter — which lowers output — and some energy is lost in dust, wiring and the inverter. This calculator estimates the DC output at the panels and the AC output after the inverter, either at a moment or as daily energy from peak sun hours.
All results are estimates for the values entered, not guaranteed generation.
Formula
Tcell = Tamb + (NOCT − 20) ÷ 800 × G PDC = N × PSTC × (G ÷ 1000) × [1 + γ (Tcell − 25)] × (1 − LDC)
PAC = min(PDC × ηinv, AC limit) EDC = N × PSTC × PSH × [1 + γ (T̄cell − 25)] × (1 − LDC) EAC = EDC × ηinv
G = irradiance on the panel (W/m²), NOCT = nominal operating cell temperature (°C), γ = power temperature coefficient (negative, per °C), LDC = DC losses, PSH = peak sun hours, T̄cell = average cell temperature during sunny hours.
Worked example
- One 550 W panel at 800 W/m², 35 °C air, NOCT 45 °C, γ −0.35 %/°C, DC losses 7%, inverter 96%: Tcell = 35 + 25 ÷ 800 × 800 = 60 °C; factor 1 − 0.0035 × 35 = 0.8775 → PDC = 359.1 W, PAC = 344.7 W.
- Daily: 5.5 peak sun hours at an average cell temperature of 50 °C → factor 0.9125 → EDC = 2.567 kWh, EAC = 2.464 kWh/day.
Assumptions and limitations
- Estimated output only, not guaranteed generation.
- Output is taken as proportional to irradiance, with a linear temperature correction from the data-sheet coefficient. Low-light efficiency, angle of incidence and spectrum are not modelled.
- The NOCT method estimates cell temperature for an open-rack mounting with light wind; roof-mounted panels with little air gap run hotter.
- The daily estimate uses one average cell temperature and ignores shading, clipping during the day, AC cable losses and ageing.
References
- IEC 61215 / IEC 61853 — module rating and NOCT (nominal operating cell temperature) conditions.
- Dobos, A. P. (2014), PVWatts Version 5 Manual, NREL/TP-6A20-62641 (temperature correction and default losses).