About this calculator
A transformer changes an AC voltage using two coils (windings) on a shared iron core. In an ideal transformer, the voltage on each winding is proportional to its number of turns: twice as many turns on the secondary gives twice the voltage. Use this calculator to find the secondary voltage from the turns, the number of secondary turns for a voltage you want, or the turns ratio needed between two voltages.
The turns ratio is a property of the windings. The actual output voltage under load is a little lower, because of winding resistance and leakage reactance — this is called voltage regulation.
Formula
Find secondary voltage
Vp ÷ Vs = Np ÷ Ns = a so Vs = Vp × Ns ÷ Np
Ip = Is ÷ a (ideal)
V = winding voltage, N = number of turns, I = current, a = turns ratio, p = primary, s = secondary.
Find secondary turns
Ns = Np × Vs ÷ Vp
Ip = Is × Ns ÷ Np (ideal)
V = winding voltage, N = number of turns, I = current, p = primary, s = secondary.
Find ratio from voltages
a = Np ÷ Ns = Vp ÷ Vs
a > 1: step-down; a < 1: step-up; a = 1: isolation transformer.
Worked example
- Secondary voltage: 230 V on a 1000-turn primary with a 50-turn secondary. Ratio = 1000 ÷ 50 = 20 : 1; Vs = 230 ÷ 20 = 11.5 V. If the secondary supplies 10 A, the ideal primary current is 10 ÷ 20 = 0.5 A.
- Secondary turns: for 24 V from 230 V with 920 primary turns: Ns = 920 × 24 ÷ 230 = 96 turns.
- Ratio: 11 kV to 433 V: a = 11 000 ÷ 433 = 25.40 : 1 (step-down).
Assumptions and limitations
- Ideal transformer: no winding resistance, no leakage, no magnetising current and no core losses. Power in equals power out.
- The ideal secondary voltage is the no-load voltage. Under load, real transformers give a slightly lower voltage; the manufacturer’s data gives the regulation.
- For a three-phase transformer, the ratio of line voltages also depends on the winding connection (for example delta–star). Use winding (phase) voltages for the turns ratio.
- The calculator does not check core size, flux density, wire size, insulation or temperature rise.
Safety note
Mains and high-voltage transformers can be lethal. Winding, testing and connecting transformers must be done by a qualified person following the applicable safety rules.
References
- Ideal transformer relations: Vp/Vs = Np/Ns = Is/Ip (standard electrical engineering texts; IEC 60076 terminology).