About this calculator
A generator must supply three things: the real power (kW) of the loads, the apparent power (kVA) their power factor requires, and the short starting surge when a motor starts. Generator sets are rated in kVA at a power factor of usually 0.8, so their kW rating is 0.8 × kVA.
List your loads with their running power, power factor and, for motors, the starting multiplier. Mark loads that start at the same moment; all others are assumed to start one at a time, which is how most installations are arranged. The calculator adds the loads as real and reactive power, applies a demand factor and design margin, checks the worst starting event, and gives an estimated rating. For the background on kW, kVA and power factor see the Power Factor article.
Formula
Per load: Pi = ni × Punit Si = Pi ÷ PFi Qi = Pi × tan(cos⁻¹ PFi)
Running: P = d × ΣPi Q = d × ΣQi S = √(P² + Q²) kVA = kW ÷ PF
Starting step: (k − 1) × S of what starts (one unit, or the whole “together” group) Sstart = S + largest step
Rating (kVA) = max[ S × (1 + m), P × (1 + m) ÷ PFgen, Sstart ] rated kW = rating × PFgen
n = quantity, PF = power factor, d = demand factor, k = starting multiplier (starting kVA ÷ running kVA), m = design margin, PFgen = generator rated power factor (usually 0.8).
Worked example
- One resistive load of 20 kW at PF 0.8, margin 20%, generator PF 0.8: running S = 20 ÷ 0.8 = 25 kVA; with margin 25 × 1.2 = 30 kVA; real-power check 20 × 1.2 ÷ 0.8 = 30 kVA; no starting surge → 30 kVA = 24 kW (margin 5 kVA / 4 kW).
- Default list (lighting, pump with ×6 start, two air conditioners, computers, fridge): running 11.8 kW / 12.98 kVA (PF 0.909); the pump start adds (6 − 1) × 6.471 = 32.35 kVA, giving 45.34 kVA. Motor starting sets the size: about 45.3 kVA (36.3 kW). A soft starter on the pump (k ≈ 2.5) would reduce this a lot.
Assumptions and limitations
- Running loads are added as real and reactive power (vectors), not by adding kVA.
- During a start every other load is assumed to be running already; only the largest starting event is checked. Loads marked “together” start in one event; all others start one unit at a time.
- Starting kVA = multiplier × running kVA, added directly to the running kVA (a cautious upper bound, because starting kVA has a low power factor).
- The rating must also cover the starting demand as a continuous kVA — a simple, cautious rule. Many generators can supply more kVA for a few seconds; check the manufacturer’s motor-starting kVA and voltage-dip data.
- Not included: voltage, phase balance, frequency, altitude and temperature derating, harmonics of non-linear loads, standby/prime duty rating, and future load growth beyond the margin.
- An estimate only; it does not replace a professional generator or load study.
References
- ISO 8528-1 — rating of reciprocating internal-combustion-engine driven generating sets (kVA rating at power factor 0.8, prime and standby ratings).
- IEEE Std 446 (Orange Book) — emergency and standby power systems, motor starting on generators.