About this calculator
Air changes per hour (ACH) tells you how many times in one hour a volume of air equal to the room’s volume is supplied to, or extracted from, the room. It is a simple way to compare ventilation rates of rooms of different sizes and is used, for example, to size exhaust fans or check a ventilation design.
Required ventilation rates depend on the room’s use, its occupants and the code or standard that applies (for example ASHRAE 62.1 / 62.2 or national building regulations). Many standards specify airflow per person or per floor area rather than ACH, so this calculator does not suggest a value.
Formula
Find ACH
ACH = V̇ × 3600 ÷ Vroom (V̇ in m³/s, Vroom in m³)
ACH = m³/h ÷ m³ ACH = cfm × 60 ÷ ft³
Vroom = length × width × height. One air change takes 60 ÷ ACH minutes.
Airflow for a target ACH
V̇ (m³/h) = ACH × Vroom (m³) cfm = ACH × ft³ ÷ 60
The airflow needed to give a target number of air changes in a room of volume Vroom.
Worked example
- A room 5 m × 4 m × 3 m has a volume of 60 m³. With 120 m³/h of ventilation: ACH = 120 ÷ 60 = 2 air changes per hour (one every 30 minutes).
- For 6 ACH in the same room: 6 × 60 = 360 m³/h = 100 L/s.
- Inch-pound: a 20 ft × 15 ft × 10 ft room (3000 ft³) with 300 cfm → 300 × 60 ÷ 3000 = 6 ACH.
Assumptions and limitations
- ACH is a volume ratio. It assumes the airflow is distributed through the whole room; with poor air mixing, parts of the room are ventilated much less.
- Use the outdoor or treated airflow that actually enters the room. Recirculated air in a fan-coil or split unit does not ventilate the room.
- Furniture and equipment are not subtracted from the room volume, as is usual practice.
- This calculator does not state a required ACH. Use the standard, code or design brief that applies to your building.
References
- ASHRAE Standard 62.1 (commercial) and 62.2 (residential): ventilation and acceptable indoor air quality — for required ventilation rates.
- Definition: air change rate = ventilation airflow ÷ room volume.