About this calculator
The U-value (thermal transmittance) tells you how much heat passes through 1 m² of a wall, roof, floor or window for each 1 K of temperature difference between the air on the two sides. A lower U-value means better insulation. It is the main number used to compare building elements and to estimate heat loss in winter and conduction heat gain in summer.
Three different quantities are involved and are often confused:
- Thermal conductivity λ (or k), in W/(m·K), is a property of a material. It does not depend on thickness.
- Thermal resistance R, in m²·K/W, belongs to a layer of a given thickness: R = d ÷ λ. Resistances of layers in series add up.
- U-value, in W/(m²·K), belongs to the whole element including the air films on both surfaces: U = 1 ÷ Rtotal.
Formula
U from layers
Rlayer = d ÷ λ Rt = Rsi + R1 + R2 + … + Rse U = 1 ÷ Rt
Q = U × A × ΔT
d = layer thickness (m), λ = thermal conductivity (W/(m·K)), Rsi and Rse = inside and outside surface resistances (m²·K/W), A = area (m²), ΔT = air temperature difference (K), Q = heat flow (W).
Surface resistances used for the standard choices (plane surfaces in still indoor air and outdoor air, ISO 6946): Rsi = 0.13 for horizontal heat flow, 0.10 for upward and 0.17 for downward heat flow; Rse = 0.04.
Inch-pound: R-values in h·ft²·°F/Btu add the same way, and U (Btu/(h·ft²·°F)) = 1 ÷ R. 1 W/(m²·K) = 0.1761 Btu/(h·ft²·°F).
Heat flow from a known U
Q = U × A × ΔT R = 1 ÷ U
The steady heat flow through an element of known U-value and area for a given air temperature difference.
Worked example
An example wall (the default values): 110 mm brick (λ = 0.77 W/(m·K)), 100 mm mineral wool (λ = 0.035) and 12.5 mm plasterboard (λ = 0.25), with horizontal heat flow.
- Rbrick = 0.110 ÷ 0.77 = 0.1429; Rwool = 0.100 ÷ 0.035 = 2.8571; Rboard = 0.0125 ÷ 0.25 = 0.0500 m²·K/W.
- Rt = 0.13 + 0.1429 + 2.8571 + 0.0500 + 0.04 = 3.2200 m²·K/W → U = 1 ÷ 3.22 = 0.311 W/(m²·K) (0.0547 Btu/(h·ft²·°F); R-value 18.3 h·ft²·°F/Btu).
- For 10 m² and ΔT = 20 K: Q = 0.311 × 10 × 20 = 62.1 W.
- Notice that the insulation gives almost 90% of the total resistance.
The λ values above are only an example. Use the manufacturer’s declared value or a recognized table (for example ISO 10456 or CIBSE Guide A) for your materials.
Assumptions and limitations
- One-dimensional steady heat flow through flat, uniform layers in series.
- Thermal bridges are not included: studs, joists, wall ties, window frames and mortar joints carry extra heat, so the real U-value is higher. ISO 6946 gives corrections for these.
- Moisture is not included. Wet insulation and wet masonry conduct much more heat than their dry λ values.
- Air gaps: do not enter an air cavity as a thickness with λ of air. Heat crosses a cavity by convection and radiation as well, so enter the cavity’s R from a recognized table (ISO 6946) in the “Additional thermal resistance” box.
- The standard surface resistances are for still indoor air and normal outdoor exposure. Strong wind, sheltered or reflective surfaces need different values; choose “Enter my own surface resistances”.
- Solar heating of sunlit walls and roofs is not included in Q = U × A × ΔT. For cooling loads use an equivalent temperature difference (see the AC Cooling Load Estimator).
- Ground floors and basement walls lose heat to the ground in a different way (ISO 13370); this calculator does not cover that.
- Enter ΔT as a positive size of the difference. The same Q applies to heat loss in winter and conduction heat gain in summer; heat flows from the warm side to the cold side.
References
- ISO 6946 — Building components and building elements: thermal resistance and thermal transmittance, calculation methods (surface resistances, layers in series).
- ISO 10456 — Building materials and products: hygrothermal properties, tabulated design values (λ).
- ASHRAE Handbook — Fundamentals, chapters on heat transfer and thermal and moisture control in insulated assemblies.