About this calculator
Air carries heat in two ways. Sensible heat changes the air’s temperature — what a thermometer shows. Latent heat is the energy in its water vapour: it is removed when a cooling coil condenses moisture out of the air, and added when air is humidified. Use this calculator to find the heat picked up or removed by supply air, outside air or air passing a coil, or to size the airflow for a room’s sensible load.
It uses the basic energy balance for moist air with property values you can change. It does not calculate a building’s cooling load; that needs a full load calculation.
Formula
Heat from airflow
Qs = ρ × V̇ × cp × ΔT
QL = ρ × V̇ × hfg × ΔW Qt = Qs + QL SHR = Qs ÷ Qt
ρ = air density (kg/m³), V̇ = airflow (m³/s), cp = specific heat of air (J/(kg·K)), ΔT = temperature change (K), hfg = latent heat of water vapour (J/kg), ΔW = change in humidity ratio (kg of water per kg of dry air).
With the default values, ρ × cp = 1.2 × 1.006 = 1.207 kJ/(m³·K). In inch-pound units the same values give the familiar rule Qs (Btu/h) = 1.08 × cfm × ΔT (°F). For latent heat the inch-pound rule 0.68 × cfm × Δgr/lb uses slightly different property values, so it gives results about 1–2% lower than this calculator.
Airflow for a load
V̇ = Qs ÷ (ρ × cp × ΔT)
The airflow needed to carry a sensible heat load Qs with a temperature change ΔT. Inch-pound form: cfm = Btu/h ÷ (1.08 × ΔT °F).
ΔT for a load
ΔT = Qs ÷ (ρ × V̇ × cp)
The temperature change of an airflow V̇ carrying a sensible heat load Qs. Inch-pound form: ΔT (°F) = Btu/h ÷ (1.08 × cfm).
Worked example
- Sensible heat: 0.5 m³/s cooled by 10 K → Qs = 1.2 × 0.5 × 1.006 × 10 = 6.04 kW.
- Latent heat: the same air loses 2 g/kg of moisture (ΔW = 0.002) → QL = 1.2 × 0.5 × 2501 × 0.002 = 3.00 kW; total 9.04 kW; SHR = 6.04 ÷ 9.04 = 0.67.
- Inch-pound check: 1000 cfm with ΔT = 20 °F → 1.08 × 1000 × 20 = 21 600 Btu/h (1.8 TR).
- Airflow for a load: a 6 kW sensible load with a 10 K supply-air temperature difference needs 6 ÷ (1.2 × 1.006 × 10) = 0.497 m³/s (about 1790 m³/h).
Assumptions and limitations
- Steady flow with the property values entered. The defaults are for standard air near sea level; density falls with altitude and temperature.
- Sensible and latent heat are calculated separately with constant properties. This is the usual engineering approximation; a psychrometric (enthalpy) calculation is more exact.
- ΔT and ΔW are entered as positive sizes of the change. The calculator gives the amount of heat; whether it is added to or removed from the air depends on your process (cooling or heating, dehumidifying or humidifying).
- The humidity-ratio change must come from your own data or a psychrometric chart; this calculator does not work it out from relative humidity.
- An air-side heat balance only. It is not a building cooling or heating load calculation.
References
- ASHRAE Handbook — Fundamentals, chapter “Psychrometrics” (moist-air properties; h = 1.006 t + W (2501 + 1.86 t) kJ/kg).
- First law of thermodynamics for a steady-flow air stream: Q = ṁ × cp × ΔT.